.Modelica.Electrical.QuasiStatic.SinglePhase.Examples.Transformer

Information

This examples shows the operational behavior of transformer with short circuit impedance. The transformer is loaded with constant current magnitude of 250A but variable phase angle. The angle varies from 0 to 360 degrees within one second of simulation time.

Transformer data

Plot the real part of the secondary voltage idealTransformer.v2.re on the x axis and idealTransformer.v2.im on the y axis. The locus of this complex voltage v2 is a circle. The center of the circle is the primary supply voltage divided by the transformation ratio of n=5. Since in this experiment the load current magnitude is constant, the voltage drop across the short circuit impedance of the transformer is constant, as well. The radius of the circle is equal to the constant magnitude of the voltage drop across the short circuit impedance.


Generated at 2020-06-05T21:39:08Z by OpenModelica 1.16.0~dev-442-g2e5bc9f