.Modelica.Electrical.Machines.Interfaces.PartialBasicTransformer

Information

Partial model of a three-phase transformer, containing primary and secondary resistances and stray inductances, as well as the iron core. Circuit layout (vector group) of primary and secondary windings have to be defined.
Default values for transformer's parameters (a realistic example) are:
turns ratio n 1
nominal frequency fNominal 50 Hz
nominal voltage per phase 100 V RMS
nominal current per phase 100 A RMS
nominal apparent power 30 kVA
primary resistance R1 0.005 Ohm per phase at reference temperature
reference temperature T1Ref 20 °C
temperature coefficient alpha20_1 0 1/K
primary stray inductance L1sigma 78E-6 H per phase
secondary resistance R2 0.005 Ohm per phase at reference temperature
reference temperature T2Ref 20 °C
temperature coefficient alpha20_2 0 1/K
secondary stray inductance L2sigma 78E-6 H per phase
operational temperature T1Operational 20 °C
operational temperature T2Operational 20 °C
These values give the operational parameters:
nominal voltage drop 0.05 p.u.
nominal copper losses 300 W

Generated at 2020-06-05T07:38:22Z by OpenModelica 1.16.0~dev-420-gc007a39