This block models the functionality of a soft starter controller, controlling the output vRef in the range [0,1] with respect to nominal voltage.

Boolean input start = true causes the output vRef to be risen according to a ramp: vRef = vStart + (1 - vStart)*(time - t0)/tRampUp.

In case the current exceeds the specified maximum current iMax during the starting ramp, the ramp is stopped. When the current falls below the lower threshold of current control iMin < iMax, the ramp is continued.

Note: It is recommended to filter the measured current, e.g. using Modelica.Blocks.Continuous.Filter

Boolean input start = false causes the output vRef to be lowered according to a ramp: vRef = -(time - t0)/tRampDown.

Parameters (6)

tRampUp

Value:

Type: Time (s)

Description: Start ramp duration

vStart

Value: 0

Type: Real

Description: Start voltage / nominal voltage

iMax

Value:

Type: Real

Description: Maximum current / nominal current

iMin

Value: 0.9 * iMax

Type: Real

Description: Lower threshold of current control

INominal

Value:

Type: Current (A)

Description: Nominal current

tRampDown

Value:

Type: Time (s)

Description: Stop ramp duration

Connectors (3)

iRMS

Type: RealInput

Description: Measured RMS current

vRef

Type: RealOutput

Description: Reference voltage

start

Type: BooleanInput

Used in Examples (1)

SoftStarter

Modelica.Electrical.PowerConverters.Examples.ACAC

Soft start of an induction machine